Heat Pump Cost & Heat Loss
Compare running costs, explore seasonal performance and estimate whole-building heat loss. Planning estimates with editable assumptions.
Compare running costs, explore seasonal performance and estimate whole-building heat loss. Planning estimates with editable assumptions.
Read the worked examples and planning guide →
Set useful heat and SCOP, then choose a fuel and tariff. The results compare the same delivered heat.
Useful heat is heat delivered after boiler losses: 12,000 purchased gas kWh × 90% = 10,800 useful kWh. The 12,000 kWh starting value above is illustrative and independent of the heat-loss estimate below.
SCOP is whole-system seasonal performance for all included heat, including hot water and relevant auxiliaries. A SCOP of 3 delivers 3 kWh of heat per kWh of electricity.
Check supplier windows and eligibility. Structures checked 1 November 2026; enter your regional quoted rates and expected shares of heat-pump electricity use. Shares are energy, not hours, and must total 100%.
Use the rates available to the direct electric system. For a flat tariff, enter the rate under Standard and leave off-peak use at 0%.
Use the share of electricity consumed. The rest is charged at the standard rate. The comparison assumes resistance heating and excludes storage losses.
User-supplied battery example: 9p/kWh delivered already includes losses. No second battery-loss adjustment is applied. The user’s 7.48p/kWh import reference is not a verified supplier offer. This assumes all heat-pump electricity is available at the entered delivered price; check capacity, charging windows and winter demand.
| Heating | Purchased kWh | Annual cost |
|---|
Ready to check what works for your site? These figures are an estimate; a site assessment comes next.
Discuss your project →Back to the serviceEnergy costs only: excludes capital cost, maintenance and standing charges. A gas standing charge is avoided only if the gas supply can actually be removed. Time-of-use prices need a consumption profile; the cheapest window alone is not an annual cost.
Snapshot checked 1 November 2026: electricity 26.32p/kWh and gas 7.97p/kWh are Ofgem average Direct Debit rates for 1 October–31 December 2026. Oil 116.80p/litre including VAT is the BoilerJuice UK indicative 1,000-litre average for 1 November. Regional prices, payment method and delivered quotes vary. This is not a live price feed.
Heat-pump electricity = useful heat ÷ SCOP. Boiler fuel = useful heat ÷ operating efficiency. All boiler efficiencies here use a gross / higher-heating-value (HHV) planning basis, capped below 100%; do not enter a net/LHV rating unchanged. Oil litres = purchased oil kWh ÷ the editable 10.35 kWh/litre planning assumption (heating-oil reference). Confirm the fuel’s gross energy content and the boiler’s gross operating efficiency with the supplier. Custom fuel is priced per useful kWh, after any fuel-system losses.
LPG means propane here. Bulk fuel uses p/litre ÷ kWh/litre. A bottled refill uses £ per 47kg ÷ (47 × kWh/kg). Both then apply the separate LPG boiler efficiency. Editable propane assumptions are 7.08 kWh/litre and 14.019 kWh/kg, informed by Flogas fuel conversions on a gross/HHV planning basis; that FAQ does not explicitly label HHV/LHV, so confirm your supplied fuel basis. The 70p/litre bulk input is illustrative: Calor requires a quote. The £112 bottled example is a London Gases 47kg refill including VAT, checked 1 November 2026 for its regional delivery area; it is not a national price. Obtain a local delivered quote and allow separately for tank rental, cylinder deposits and equipment.
Condensing/non-condensing selections set editable operating examples (gas/LPG 90% or 75%; oil 85% or 75%). They are planning assumptions, not ratings for every boiler. Energy Saving Trust explains boiler types; use the actual model and installation evidence to refine annual performance.
Break-even SCOP = electricity p/kWh × boiler efficiency ÷ fuel p/kWh. Percentage difference uses the selected comparator’s cost. Free fuel or zero demand makes the percentage unavailable. Seasonal performance requires system design and operating evidence; it cannot be inferred from flow temperature alone.
Compare daily battery shifting with outage capacity · Continue to the building heat-loss estimate
Screening estimate only. Total floor area includes every storey; exposed element areas are entered separately. The result excludes hot-water recovery and any plant-sizing uplift.
This illustrative insulated home gives about 4.73kW space-heating loss at 21°C indoors and −1°C outdoors. Change the inputs for your building.
A detached 10m × 7.5m rectangle, two 2.5m storeys: 75m² footprint, 375m³ heated volume and 175m² gross external wall. Subtract 25m² windows and 3m² doors to give 147m² net wall. The 75m² roof boundary is the insulated ceiling below an unheated loft.
Insulated cavity walls, insulated ground floor and modern double glazing are illustrative starting values, not surveyed construction. Thermal bridges, detailed ground transfer and boundary corrections need a full room-by-room design.