Buffer & Water Volume Planner
Estimate the fluid volume needed to absorb minimum-output surplus for one run, then compare it with the volume already participating.
A volume allowance does not establish heat-pump capacity, safe defrost, hydraulic layout or pump selection. Use manufacturer limits and a system design before choosing equipment.
Your volume estimate
Additional participating volume
The estimate credits only the water volume that remains connected and circulating in the operating condition you entered. Confirm that volume and the manufacturer minimum before selecting a vessel.
Cycling-volume allowance
Total volume to absorb the modelled surplus for the chosen on-time.
Circuit fluid flow
At the entered heat duty and flow-to-return difference.
How the figures relate
Assumptions and calculation method
Surplus heat = max(0, minimum heat-pump output − concurrent active load). Required cycling volume = surplus kW × on-time minutes × 60 ÷ (fluid heat capacity kJ/litre·K × usable temperature rise K).
Required participating volume is the larger of the cycling allowance and the entered manufacturer minimum. Additional volume = max(0, required volume − existing participating volume). These are concurrent minimum-volume tests; they are not added together.
Fluid flow in litres/minute = circuit kW × 60 ÷ (fluid heat capacity × flow-to-return difference). A heat pump's flow temperature alone does not establish this difference. Pipe resistance, pump curves and manufacturer minimum/maximum flow still require checking.
The model assumes constant source output, constant load and well-mixed fluid over one on-cycle. Stratification, control sensors, bypasses, zone valves and pipe arrangements affect usable volume. Existing-water credit is valid only if that water remains in circuit and participates through the entered temperature band. With no surplus, this model has no minimum-runtime cycling-volume requirement; other requirements still apply.
Defrost energy, minimum allowable return temperature, freeze protection and manufacturer hydraulic requirements are not derived here. If the manufacturer minimum is left at zero, no manufacturer or defrost requirement has been checked. The tool does not recommend two-, three- or four-pipe layouts or issue a plant-sizing pass.
Method reference: Caleffi: design details for air-to-water heat pumps, using the same surplus-energy balance converted to SI units. Minimum output, on-time and temperature band are entered assumptions, not validated data for a selected product.
Review building heat loss · Discuss a detailed heating-system design